¼³°è Á¶°Ç(Design Condition) |
|
|
¨ç Qualified Life : 41 Years |
|
|
¨è Temperature : Max. 122¢µ (50¡É) |
|
|
¨é Relative Humidity : Max. 90% |
|
|
¨ê Pressure : Atmospheric (0 Psig) |
|
|
¨ë Radiation : 1.0E4 rads Gamma (TID) |
|
|
¨ì Seismic : |
|
|
- Generic Spectra (10g Peak and 4g ZPA) as specified IEEE C37.98-1987 |
|
|
- Test Response Spectra addressed in PBS Test Report, TR 20014, |
|
|
¡°Seismic Test Report HVAC Control Panels for Korea Electric |
|
|
Company Ulchin 5&6 Nuclear Power Plant. |
|
|
- Damping Factor : OBE 2%, SSE 5% |